| Cooling air flow field in the primary mirror temperature control system of a solar telescope | |
Yu JZ(喻进知) ; Gu BZ(顾伯忠) ; Jiang X(姜翔) ; Zhao T(赵特)
| |
| 2024-08-30 | |
| 发表期刊 | Journal of Instrumentation
![]() |
| 卷号 | 19期号:8页码:P08031-1-17 |
| 摘要 | The temperature distribution and the difference with the ambient temperature of the primary mirror are crucial factors affecting the observational quality of the solar telescope. We designed a flow field structure of the primary mirror temperature control system based on the 2.5-meter Wide-field and High-resolution Solar Telescope(WeHoT),analyzed the flow conditions and heat transfer capacity of the overall flow field,and then carried out five stages of optimization iteration and simulation guided by the analysis results.A flow field structure for the primary mirror temperature control system with high efficiency and high uniformity is summarized. The simulation results for the final solution indicate an average surface temperature of the primary mirror at 20.064◦C,with a maximum temperature difference within the reflective surface of 0.809◦C,and a reduced difference with the ambient temperature of 0.411◦C.Surface thermal deformation is less than 0.2μm,with an RMS value of 18.05 nm,achieving the ideal state. This work can provide a theoretical foundation and valuable insights for future research on the temperature control system of the primary mirror in large-aperture solar telescopes. |
| 关键词 | Instrument optimisation Detector design and construction technologies and materials Detector cooling and thermo-stabilization |
| 学科领域 | 天文技术与方法 |
| 语种 | 英语 |
| 文献类型 | 期刊论文 |
| 条目标识符 | http://ir.niaot.ac.cn/handle/114a32/2260 |
| 专题 | 中国科学院南京天文光学技术研究所知识成果 期刊论文 |
| 作者单位 | 南京天文光学技术研究所 |
| 推荐引用方式 GB/T 7714 | Yu JZ,Gu BZ,Jiang X,et al. Cooling air flow field in the primary mirror temperature control system of a solar telescope[J]. Journal of Instrumentation,2024,19(8):P08031-1-17. |
| APA | Yu JZ,Gu BZ,Jiang X,&Zhao T.(2024).Cooling air flow field in the primary mirror temperature control system of a solar telescope.Journal of Instrumentation,19(8),P08031-1-17. |
| MLA | Yu JZ,et al."Cooling air flow field in the primary mirror temperature control system of a solar telescope".Journal of Instrumentation 19.8(2024):P08031-1-17. |
| 条目包含的文件 | 下载所有文件 | |||||
| 文件名称/大小 | 文献类型 | 版本类型 | 开放类型 | 使用许可 | ||
| Cooling air flow fie(8201KB) | 期刊论文 | 出版稿 | 开放获取 | CC BY-NC-SA | 浏览 下载 | |